Technical specifications
| Power | DC24V |
|---|---|
| Current | Monitoring current: ≤ 70μA Alarm current: ≤ 15mA |
| Indicator | Red LED Polling: Flash every 6 seconds Alarm: Remain lit Fault: Flash every 2 seconds |
| Alarm Threshold for Heat Detection | A2R (54°C to 62°C) (129°F to 144°F) |
| Wiring | Two-wire, polarity-free |
| Operating Temperature | –10°C to +55°C (+14°F to +131°F) |
| Storage Temperature | –20°C to +65°C (–4°F to +149°F) |
| Operating Humidity | ≤ 95% RH (no condensation) |
| Color | White |
| Dimensions (with base) | Φ 100 mm × 68.7 mm (Φ 3.94" × 2.70") |
| Weight (with base) | 110.0 g (0.243 lb) |
| Compliance Standard | EN54-5, EN54-7 |